48 × 96 mm. Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications.
Power supply voltage | An in-model number: 100 to 240 VAC, 50/60 Hz |
Operating voltage range | 85 to 110% of the rated supply voltage |
Power consumption | 5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U.N, R, S, B, C/W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, O0to5V,orO0to 10 V |
HAR Repecanice | Current input: 150 Q max., Voltage input: 1 MQ min. (Use a 1:1 connection when connecting the ES2-HB-N/THB-N.} |
Control method | ON/OFF control or 2-PID control (with auto-tuning) |
Say Copa | SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
pate Voltage output P (for driving SSR) | Output voltage 12 VDC +20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit P 9 …… …… P |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Q max., resolution: Approx. 10,000 |
several outputs Auxiliary | 1 or 2 (depending on the model) |
— Output specifications | SPST-NO relay outputs, 250 VAC, 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) |
Number of inputs | 1 or 2 (depending on the model) |
Event | Contact input ON: 1 kQ max., OFF: 100 kQ min. |
input Suet specifications | Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max. |
Current flow: approx. 7 mA per contact | |
Setting method | Digital setting using front panel keys |
an year | 11-segment digital displays and individual indicators Character height: PV: 10.5 mm, SV: 5.0 mm |
Multi SP | Up to eight set points (SPO to SP7) can be saved and selected using the event inputs, key operations, or; Labs serial communications. * |
Bank switching | None |
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, display brightness setting, simple transfer output, and work bit message |
Ambient operating temperature | ~10 to 55°C (with no condensation or icing), For 3-year warranty: —10 to 50°C with standard mounting (with no condensation or icing) |
Ambient operating humidity | 25 to 85% |
Storage temperature | ~25 to 65°C (with no condensation or icing) |
Altitude | 2,000 m max. |
Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity |
Installation environment | Overvoltage category !|, Pollution Degree 2 (EN/IEC/UL 61010-1) |