PF | Sensor Inductive Type NJ2-V3-N  6,000
Description
Inductive sensor NJ2-V3-N

General specifications

Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance2 mm
Installationflush
Assured operating distance0 … 1.62 mm
Reduction factor rAl0.25
Reduction factor rCu0.2
Reduction factor r3040.7
Output type2-wire

Nominal ratings

Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 … 1000 Hz
Hysteresis0.01 … 0.1 mm
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption 
 Measuring plate not detected≥ 3 mA
 Measuring plate detected≤ 1 mA

Functional safety related parameters

Safety Integrity Level (SIL)SIL 2
MTTFd11775 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %

Compliance with standards and directives

Standard conformity 
 NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
 StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012

Approvals and certificates

IECEx approval 
 Equipment protection level GaIECEx PTB 11.0021X
 Equipment protection level GbIECEx PTB 11.0021X
 Equipment protection level DaIECEx PTB 11.0021X
 Equipment protection level MbIECEx PTB 11.0021X
ATEX approval 
 Equipment protection level GaPTB 00 ATEX 2032 X
 Equipment protection level GbPTB 00 ATEX 2032 X
 Equipment protection level DaPTB 00 ATEX 2032 X
UL approval 
 Ordinary LocationE87056
 Hazardous LocationE501628
 Control drawing116-0451
CCC approval 
 Hazardous Location2020322315002302
NEPSI approval 
 NEPSI certificateGYJ16.1394X
CML approvalon request
ANZEx19.3001X

Ambient conditions

Ambient temperature-25 … 100 °C (-13 … 212 °F)

Mechanical specifications

Connection typecable
Housing materialPBT
Sensing facePBT
Degree of protectionIP67
Cable 
 Cable diameter2.6 mm ± 0.2 mm
 Bending radius> 10 x cable diameter
 MaterialPVC
 Core cross section0.14 mm2
 Length130 mm
Dimensions 
 Height10.2 mm
 Width27.8 mm
 Length16 mm

 

datesheet
Data Sheet
NJ2-V3-N
1.6 MB
Additional information
delivery

Local Pickup